Return to site

Peak Hour 4 1 95

broken image


  1. Peak Hour 4 1 95 Resz
  2. Peak Hour 4 1 95 Mph
  3. Peak Hour 4 1 95 Fm Radio

Sudbury police seek help in locating 34-year-old woman last seen more than a week ago. Check out Peak Hour Music on Beatport. Welcome to Beatport. Beatport is the world's largest electronic music store for DJs.

2018 DatesHour2019 DatesHour
June 185 PMJuly 106 PM
July 275 PMJuly 175 PM
August 285 PMJuly 196 PM
September 45 PMJuly 295 PM
September 55 PMAugust 195 PM

The employer shall administer a continuing, effective hearing conservation program, as described in paragraphs (c) through (o) of this section, whenever employee noise exposures equal or exceed an 8-hour time-weighted average sound level (TWA) of 85 decibels measured on the A scale (slow response) or, equivalently, a dose of fifty percent. Add this station to your favourites These features, and others, are powered by cookies OK. A time-of-use plan charges less money for electricity used at off-peak hours of the day and more for on-peak hours. At APS, the on-peak hours are 3-8 p.m. There are no weekend on-peak hours.

In accordance with the PJM RAA and PJM rules and procedures, BGE will calculate a system capacity peak load contribution (capacity PLC) 'ticket' for each electric account on an annual basis. After the end of a summer period, PJM will identify the five highest PJM system coincident load hours that occurred on different days over the period from June 1 to September 30. The local distribution company (LDC)-specific zones will identify the actual zonal loads associated with these five hours. Each LDC-specific zone will reconcile these five different hours back to the one hour weather normalized, system coincident zonal peak load obligation. The consequent peak load contributions will be calculated as an average over these five hours. Each account's PLC will be updated on a yearly basis in accordance with PJM rules and procedures, with supporting data posted on BGE's Web site. The five days and 'hour ending' times in 2019 and 2020 used to calculate the year 2019/2020 & 2020/2021 capacity PLCs respectively, are as follows:

2019/2020 & 2020/2021 Defaults for Capacity Peak Load Contributions

In addition to calculating a system capacity PLC 'ticket' for each electric account on an annual basis, BGE also determines an average system capacity PLC for each BGE customer segment. These averages are used as the default system capacity PLC for any electric account that is established with BGE after the five highest system capacity hours have occurred (see above). Each default PLC will be updated on a yearly basis in accordance with PJM rules and procedures and posted on BGE's Web Site. The default system capacity PLCs for 2018 & 2019 by customer segment are as follows:

Peak Hour 4 1 95 Resz

Peak hour 4
SegmentDescriptionTariff CodesDefault PLC(effective 6/1/19 - 5/31/20)Default PLC(effective 6/1/20 - 5/31/21)
RResidential
(non-electric heat)
40, 412.58 kW2.69 kW
RHResidential
(electric heat)
42, 432.60 kW2.72 kW
RLResidential Time-of-Use
(non-electric heat)
443.69 kW3.76 kW
RLHResidential Time-of-Use
(electric heat)
453.63 kW3.66 kW
GGeneral Service
(< 60 kW)
50, 52, 535.33 kW5.28 kW
GSGeneral Service
Time-of-Use (< 60 kW)
55, 5618.19 kW18.17 kW
GLGeneral Service Large
Time-of-Use (> 60 kW)
65 - 69123.22 kW119.28 kW
GLPGeneral Service Large
Time-of-Use (> 60 kW)

70 - 73 (13kV voltage)
76-79 (34 kV voltage)

2048.69 kW
2938.94 kW

1998.62 kW
2889.56 kW
PPrimary Service Time-of-Use 89-90 (13kV voltage)
95-96 (34 kV voltage)
2048.69 kW
2938.94 kW
1998.62 kW
2889.56 kW
TPrimary Service
Time-of-Use-Transmission Service
97 - 98 (115 kV voltage)12605.56 kW13501.68 kW

NOTE: A '1' preceding the Tariff Code denotes the account is currently enrolled with a supplier.

Peak Hours for Network Transmission Peak Load Contribution

2019 DatesHour
January 319 AM
July 175 PM
July 197 PM
July 206 PM
July 216 PM

Each local distribution company within PJM has a network transmission service peak load contribution requirement. To allocate fairly the LDC's daily requirement to electricity suppliers, network transmission service peak load contributions (transmission PLCs) are determined. In accordance with the Open Access Transmission Tariff (OATT) and PJM rules and procedures, BGE will calculate a transmission PLC 'ticket' for each electric account on an annual basis. For a given year, an account's daily network transmission service PLC requirement is based on its load at the time of the actual unrestricted peak hours that occurred during the twelve months ending October 31 of the prior calendar year. At the end of this 12-month period, PJM and BGE will identify the five highest unrestricted load hours that occurred on different days during this 12-month period. The LDC will reconcile these five different hours back to the highest unrestricted peak load hour that PJM has determined to be BGE's zonal peak load obligation. The consequent peak load contributions will be calculated as an average over these five hours. The five days and 'hour ending' times in 2019 used to calculate the year 2020 network transmission PLCs respectively, are as follows:

2020 Defaults for Transmission Peak Load Contributions

In addition to calculating a transmission PLC 'ticket' for each electric account on an annual basis, BGE also determines an average transmission PLC for each BGE customer segment. These averages are used as the default transmission PLC for any electric account that is established with BGE after the five highest transmission hours have occurred (see above). Each default PLC will be updated on a yearly basis in accordance with PJM rules and procedures and posted on BGE's Web Site. The default transmission PLCs for 2020 by customer segment are as follows:

SegmentDescriptionTariff Codes2020 Default PLC
RResidential
(non-electric heat)
40, 412.72 kW
RHResidential
(electric heat)
42, 432.72 kW
RLResidential Time-of-Use
(non-electric heat)
444.01 kW
RLHResidential Time-of-Use
(electric heat)
453.91 kW
GGeneral Service
(< 60 kW)
50, 52, 535.26 kW
GSGeneral Service
Time-of-Use (< 60 kW)
55, 5619.12 kW
GLGeneral Service Large
Time-of-Use (> 60 kW)
65 - 69119.53 kW
GLPGeneral Service Large
Time-of-Use (> 60 kW)
70 - 73 (13 kV voltage)
76-79 (34 kV voltage)
2,156.73 kW
3,166.62 kW
PPrimary Service
Time-of-Use
89-90 (13 kV voltage)
95-96 (34 kV voltage)
2,256.16 kW
3,166.62 kW
TTransmission Voltage Service97-98 (115 kV voltage)15,342.97 kW

NOTE: A '1' preceding the Tariff Code denotes the account is currently enrolled with a supplier.


Peak Hour Volume, Design Flow Rate, PHF

It is commonly known in your area that the heaviest traffic flow rates occur between 4:00 PM and 6:30 PM. Your assignment for the day is to find the peak hour volume, peak hour factor (PHF), and the actual or design flow rate for an existing one-lane approach. To do this, you obtain a click-counter and position yourself at the intersection. For each fifteen-minute interval, you record the numbers of right-turns, left-turns, straight-through trucks, and straight-through passenger cars. Your tabulated values are as shown below.

Time IntervalLeft TurnsRight TurnsST TrucksST Cars
4:00-4:15510630
4:15-4:30615826
4:30-4:45471035
4:45-5:00716840
5:00-5:151013649
5:15-5:309121255
5:30-5:451415865
5:45-6:0012121050
6:00-6:15109839
6:15-6:30912430

If a truck is equal to 1.5 passenger cars and a right-turn is as well, and if a left-turn is equal to 2.5 passenger cars, then calculate the peak hour volume, peak hour factor (PHF), and the actual (design) flow rate for this approach.

[Solution Shown Below]

Solution

Peak Hour 4 1 95
SegmentDescriptionTariff CodesDefault PLC(effective 6/1/19 - 5/31/20)Default PLC(effective 6/1/20 - 5/31/21)
RResidential
(non-electric heat)
40, 412.58 kW2.69 kW
RHResidential
(electric heat)
42, 432.60 kW2.72 kW
RLResidential Time-of-Use
(non-electric heat)
443.69 kW3.76 kW
RLHResidential Time-of-Use
(electric heat)
453.63 kW3.66 kW
GGeneral Service
(< 60 kW)
50, 52, 535.33 kW5.28 kW
GSGeneral Service
Time-of-Use (< 60 kW)
55, 5618.19 kW18.17 kW
GLGeneral Service Large
Time-of-Use (> 60 kW)
65 - 69123.22 kW119.28 kW
GLPGeneral Service Large
Time-of-Use (> 60 kW)

70 - 73 (13kV voltage)
76-79 (34 kV voltage)

2048.69 kW
2938.94 kW

1998.62 kW
2889.56 kW
PPrimary Service Time-of-Use 89-90 (13kV voltage)
95-96 (34 kV voltage)
2048.69 kW
2938.94 kW
1998.62 kW
2889.56 kW
TPrimary Service
Time-of-Use-Transmission Service
97 - 98 (115 kV voltage)12605.56 kW13501.68 kW

NOTE: A '1' preceding the Tariff Code denotes the account is currently enrolled with a supplier.

Peak Hours for Network Transmission Peak Load Contribution

2019 DatesHour
January 319 AM
July 175 PM
July 197 PM
July 206 PM
July 216 PM

Each local distribution company within PJM has a network transmission service peak load contribution requirement. To allocate fairly the LDC's daily requirement to electricity suppliers, network transmission service peak load contributions (transmission PLCs) are determined. In accordance with the Open Access Transmission Tariff (OATT) and PJM rules and procedures, BGE will calculate a transmission PLC 'ticket' for each electric account on an annual basis. For a given year, an account's daily network transmission service PLC requirement is based on its load at the time of the actual unrestricted peak hours that occurred during the twelve months ending October 31 of the prior calendar year. At the end of this 12-month period, PJM and BGE will identify the five highest unrestricted load hours that occurred on different days during this 12-month period. The LDC will reconcile these five different hours back to the highest unrestricted peak load hour that PJM has determined to be BGE's zonal peak load obligation. The consequent peak load contributions will be calculated as an average over these five hours. The five days and 'hour ending' times in 2019 used to calculate the year 2020 network transmission PLCs respectively, are as follows:

2020 Defaults for Transmission Peak Load Contributions

In addition to calculating a transmission PLC 'ticket' for each electric account on an annual basis, BGE also determines an average transmission PLC for each BGE customer segment. These averages are used as the default transmission PLC for any electric account that is established with BGE after the five highest transmission hours have occurred (see above). Each default PLC will be updated on a yearly basis in accordance with PJM rules and procedures and posted on BGE's Web Site. The default transmission PLCs for 2020 by customer segment are as follows:

SegmentDescriptionTariff Codes2020 Default PLC
RResidential
(non-electric heat)
40, 412.72 kW
RHResidential
(electric heat)
42, 432.72 kW
RLResidential Time-of-Use
(non-electric heat)
444.01 kW
RLHResidential Time-of-Use
(electric heat)
453.91 kW
GGeneral Service
(< 60 kW)
50, 52, 535.26 kW
GSGeneral Service
Time-of-Use (< 60 kW)
55, 5619.12 kW
GLGeneral Service Large
Time-of-Use (> 60 kW)
65 - 69119.53 kW
GLPGeneral Service Large
Time-of-Use (> 60 kW)
70 - 73 (13 kV voltage)
76-79 (34 kV voltage)
2,156.73 kW
3,166.62 kW
PPrimary Service
Time-of-Use
89-90 (13 kV voltage)
95-96 (34 kV voltage)
2,256.16 kW
3,166.62 kW
TTransmission Voltage Service97-98 (115 kV voltage)15,342.97 kW

NOTE: A '1' preceding the Tariff Code denotes the account is currently enrolled with a supplier.


Peak Hour Volume, Design Flow Rate, PHF

It is commonly known in your area that the heaviest traffic flow rates occur between 4:00 PM and 6:30 PM. Your assignment for the day is to find the peak hour volume, peak hour factor (PHF), and the actual or design flow rate for an existing one-lane approach. To do this, you obtain a click-counter and position yourself at the intersection. For each fifteen-minute interval, you record the numbers of right-turns, left-turns, straight-through trucks, and straight-through passenger cars. Your tabulated values are as shown below.

Time IntervalLeft TurnsRight TurnsST TrucksST Cars
4:00-4:15510630
4:15-4:30615826
4:30-4:45471035
4:45-5:00716840
5:00-5:151013649
5:15-5:309121255
5:30-5:451415865
5:45-6:0012121050
6:00-6:15109839
6:15-6:30912430

If a truck is equal to 1.5 passenger cars and a right-turn is as well, and if a left-turn is equal to 2.5 passenger cars, then calculate the peak hour volume, peak hour factor (PHF), and the actual (design) flow rate for this approach.

[Solution Shown Below]

Solution

The first step in this solution is to find the total traffic volume for each 15 minute period in terms of passenger car units. This is done by multiplying the number of trucks by 1.5, the number of right turns by 1.5, and the number of left turns by 2.5. We then add these three numbers and the volume of straight-through cars together to get the total volume of traffic serviced in each interval. Once we have this, we can locate the hour with the highest volume and the 15 minute interval with the highest volume. The peak hour is shown in blue below with the peak 15 minute period shown in a darker shade of blue.

Time IntervalInterval Volume (pcu)
4:00-4:1567
4:15-4:3076
4:30-4:4571
4:45-5:0094
5:00-5:15103
5:15-5:30114
5:30-5:45135
5:45-6:00113
6:00-6:1590
6:15-6:3077

Mac backup guru 6 7 download free. The peak hour volume is just the sum of the volumes of the four 15 minute intervals within the peak hour (464 pcu). The peak 15 minute volume is 135 pcu in this case. The peak hour factor (PHF) is found by dividing the peak hour volume by four times the peak 15 minute volume. Noteburner m4v converter plus 4 3 0 download free.

Peak Hour 4 1 95 Mph

PHF = 464 /(4 * 135) = 0.86

Peak Hour 4 1 95 Fm Radio

The actual (design) flow rate can be calculated by dividing the peak hour volume by the PHF, 464/0.86 = 540 pcu/hr, or by multiplying the peak 15 minute volume by four, 4 * 135 = 540 pcu/hr.





broken image